EVACGEN-NZ

Config Jumper Assignments

Config Link 1
Installed to disable monitoring presence of the third party amplifier. 

Config Link 2
Installed to provide Evac Gen isolation when Input 4 is active 

Config Link 3
Installed to enable class change mode on Input 3. RS485 operation is not recommended in this mode 

Config Link 4
Installed when Bell Input must be active for operation of direct inputs 1-4

Defect Table

Defect Bell Circuit Monitor RS485 Message (e.g. F100) Fault LED
DC Power Supply 'Off Normal' EOL clamped to 5kΩ LED Mimic/Amp xx Defect 1st Flash Long
Amplifier Output Low or Overload EOL clamped to 5kΩ LED Mimic/Amp xx Defect 2nd Flash Long
100V Line Out 10kΩ EOL Open Circuit EOL clamped to 5kΩ LED Mimic/Amp xx Defect 3rd Flash Long
100V Line Out 10kΩ EOL Short Circuit EOL clamped to 5kΩ LED Mimic/Amp xx Defect 4th Flash Long
RS485 Communication problem EOL clamped to 5kΩ LED Mimic/Amp xx Missing 5th Flash Long
Amplifier  Monitor problem EOL clamped to 5kΩ LED Mimic/Amp xx Defect 6th Flash Long
Fault Input Activation EOL clamped to 5kΩ LED Mimic/Amp xx Defect 7th Flash Long
FIP Input O/C EOL clamped to 5kΩ LED Mimic/Amp xx Defect 8th Flash Long
Spare N/A N/A 9th Flash Long
DC Power Supply 'Off Normal' History Normal Normal 10th Flash Long
Amplifier Output Low/Overload History Normal Normal 11th Flash Long
100VLine Out 10kΩ EOL Open Circuit History Normal Normal 12th Flash Long
100VLine Out 10kΩ EOL Short Circuit History Normal Normal 13th Flash Long
RS485 Communication problem History Normal Normal 14th Flash Long
Amplifier  Monitor problem History Normal Normal 15th Flash Long
Fault Input Activation History Normal Normal 16th Flash Long
FIP Input Defect History Normal Normal 17th Flash Long
Spare N/A N/A 18th Flash Long

Tone Selection Table