F4

Masterboard Config Link Settings

Function  
Auxillary Relay Board or RMAX board fitted  
MJ5 link removed  
DBA on circuit 4. 
MJ4 link fitted  
Defect Buzzer  
MJ3 link fitted  
NZS4512: 2003 mode. 
LK1 link fitted  
NZS4512:1997 mode  
LK1 link cut  


System Fault Indication Table

Source of Defect (LD1) Position Code
Circuit 1 fault Flash 1 is long
Circuit 2 fault Flash 2 is long
Circuit 3 fault Flash 3 is long
Circuit 4 fault Flash 4 is long
Monitored Bell circuit fault Flash 5 is long
Comms failure (monitors data communications to the Aux Relay Board) Flash 6 is long
Battery Voltage Out of Range : below 12.2 Vdc or above 14.3 Vdc Flash 7 is long
20V Reference Out of Range : below 15.5 Vdc or above 26 Vdc Flash 8 is long
Earth Leakage fault Flash 9 is long
Internal Memory error Flash 10 is long
Remote Mimic Aux Fault Flash 11 is long
Remote Mimic Missing Flash 12 is long

 


Datum levels NZS4512:2010  Detector Circuit

Figure below depicts the regions for the M-value voltages and the Zone Load (RL) values when the F4 panel is operating to NZS4512:2010.

 

Datum levels for NZS4512:1997  Detector Circuit

Figure below depicts the regions for the M-value voltages and the Zone Load (RL) values when the F4 panel is operating to NZS4512:1997.  

 


Datums levels for NZS4512:2010 DBA Circuit

Figure below depicts the regions for the M-value voltages and the Zone Load (RL) values when the F4 DBA Input is operating to NZS 4512:2010.  

 

Datum levels for NZS4512:1997 DBA Circuit

Figure below depicts the regions for the M-value voltages and the Zone Load (RL) values when the F4 DBA Input is operating to NZS 4512:1997.

 

F4-RMAX

F4 Remote LED Mimic / Aux Relay Module

Compatibility
The F4-RMAX is compatible with F4 fire alarm panels fitted with version 5.02 or later firmware, and
version 5.05 or later F4 master boards.

The F4-RMAX board may be fitted in an F4 panel that also has an F4 Type 5 Sound Control Board,
provided the panel master board is version 5.05 or later.

Note: Pertronic Industries recommend that the RMAX board should be used with the standard
(flashing) mimic F100PDB12, in preference to the steady indication (F100PDB12S).


Dip Switch Settings
SW1 Not Used
SW2 Not Used
SW3 Type 5 Global Z1
SW4 LED Mimic Enable

If the panel is fitted with a F4 Type 5 Sound Control Board, then with RMAX connected
and SW3 OFF, zones 1, 2, 3 and 4 function as standard zones.